EnglishEnglish

PS-CTPT1000 Frequency Conversion Transformer Tester Ct Pt Tester

The device uses high-performance DSP and ARM, and advanced manufacturing technology to ensure stable and reliable product performance, complete functions, high automation, high test efficiency, and a leading level in the country. It is a professional testing instrument for transformers in the power industry.
DOWN LOAD TO PDF
Details
Tags
Product Selling Point Introduction

 

  1. 1、Comprehensive functions, which not only meet the excitation characteristics (ie volt-ampere characteristics), transformation ratio, polarity, secondary winding resistance, secondary load, ratio difference, and angle difference of various CTs (such as protection, measurement, TP) It can also be used to test the excitation characteristics, transformation ratio, polarity, secondary winding resistance, ratio difference and angle difference of various PT electromagnetic units.
    2、The inflection point voltage/current, 10% (5%) error curve, accuracy limit factor (ALF), instrument security factor (FS), secondary time constant (Ts), remanence factor (Kr), saturation and CT and PT parameters such as unsaturated inductance.
    3、The test meets various transformer standards such as GB1208 (IEC60044-1), GB16847 (IEC60044-6), GB1207, etc., and which standard is automatically selected for testing according to the type and level of the transformer.
    4、Based on the advanced low-frequency method test principle, it can cope with CT test with an inflection point of up to 45KV.
    5、Friendly and beautiful interface, all Chinese graphical interface.
    6、The device can store 2000 sets of test data, which will not be lost after power failure. After the test is completed, save it in the PC with a U disk, analyze the data with the software, and generate a WORD report.
    7、The test is simple and convenient. The direct resistance, excitation, transformation ratio and polarity test of CT can be completed with one key. In addition to the load test, all other CT tests use the same wiring method.
    8、Easy to carry, the weight of the device is <9Kg.

 

Product Parameter 

 

Test purpose

Protection class CT, protection class PT

Output

0~180Vrms,12Arms,18A(Peak)

CT ratio
Measurement

Scope

1~40000

 

Precision

±0.05%

PT ratio
Measurement

Scope

1~40000

 

Precision

±0.05%

Phase measurement

Precision

±5min

 

Resolution

0.5min

Secondary winding resistance measurement

Scope

0~300Ω

 

Precision

2%±2mΩ

AC load measurement

Scope

0~1000VA

 

Precision

2%±0.2VA

Input power supply voltage

AC220V±10%,50Hz

working environment

temperature:-10οC~50οC, humidity:≤90%

size and weight

Size:340mm x 300mm x 150mm weight:<9kg

 

Video

 

If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.


Write your message here and send it to us
Related News
  • Ensuring Transformer Reliability with High-Precision Turns Ratio Testing
    Ensuring Transformer Reliability with High-Precision Turns Ratio Testing
    Transformers are the heart of electrical power systems, and ensuring their performance and safety is vital to the stability of the entire power grid. Among the various tests carried out during transformer manufacturing and maintenance, turns ratio testing plays a crucial role. A transformer's turns ratio, the ratio between the number of windings in the primary and secondary coils, directly affects voltage transformation and load balancing. Even a slight deviation can be an early indicator of internal faults, winding damage, or insulation failure.
    Detail
  • Ensuring SF₆ Gas Safety: Introducing PUSH’s Integrated SF₆ Analyzer for Dew Point, Purity, and Decomposition Monitoring
    Ensuring SF₆ Gas Safety: Introducing PUSH’s Integrated SF₆ Analyzer for Dew Point, Purity, and Decomposition Monitoring
    In the power transmission and distribution industry, sulfur hexafluoride (SF₆) plays a critical role as an insulating and arc-quenching medium in high-voltage switchgear, circuit breakers, transformers, and gas-insulated substations (GIS). Its exceptional dielectric strength, chemical stability, and thermal conductivity make it the gas of choice for ensuring safety and reliability in modern electrical systems.
    Detail
  • Exploring the Main Types of Industrial Endoscopes and Their Applications Across Industries
    Exploring the Main Types of Industrial Endoscopes and Their Applications Across Industries
    In the rapidly evolving field of non-destructive testing (NDT), industrial endoscopes have become indispensable tools due to their intuitive visual inspection capabilities, non-invasive operation, and high diagnostic accuracy. Whether it’s in aerospace, automotive maintenance, energy, or security, these devices enable real-time internal observation without dismantling equipment, greatly enhancing inspection efficiency and safety.
    Detail

If you are interested in our products, you can choose to leave your information here, and we will be in touch with you shortly.